Hardware and Engineering
12/01 AWB2700-1428GB
8
Fitting XI/ON base modules
The XI/ON base modules are fitted on the right of the XC600
controller on the mounting rail:
X Fit the groove of the XI/ON base module onto the mounting rail
from underneath .
X Tilt the upper end back and press the base module against the
mounting rail until you can hear it snap into position
.
X Push the base module as far left as possible until the two snap
hooks on the side of the adapter or neighbouring base module
click into position .
X Fix the XI/ON modules using the end bracket and end plate on
the mounting rail.
X Once you have fitted all modules, switch on the 24 V power
supply on the XC-POW50-XION-UPS module in order to provide
the 5 V supply to the XI/ON modules.
X Check that the modules are working correctly (no fitting errors,
no gaps).
Engineering
Control cabinet design
The arrangement of components in the control cabinet is an impor-
tant factor in ensuring that system and machine functions are free
of interference. During the planning and design stages, as well as
during implementation, it must be ensured that the power and
control sections are separated. The power section includes the
following components:
Contactors
Coupling modules
Transformers
Frequency inverters
Current converters
Dividing the control cabinet into to areas with different power and
interference levels is recommended as an effective prevention
against electromagnetic interference. In small control cabinets,
this can often be provided sufficiently by using separators in order
to reduce interference.
h
Further information on mounting and wiring is provided in
the XI/ON manuals, e.g. Hardware and Engineering
XI/ON PROFIBUS-DP (AWB2700-1394).
1
2
3
Figure 6: Fitting XI/ON modules
2
3
1
h
Wire the base modules after they have been fitted and
before you have fitted the electronic modules!
h
Only apply the field voltage on the XC600 controller base
module after the error-free state of the station is ensured.