12/01 AWB2700-1428GB
Basic menu
43
MAIN MENU: PROGRAM
RESET
This menu contains different Reset functions:
All of these Reset commands switch the PLC to STOP and initialise
the variables. Variables declared as RETAIN, PERSISTENT or
RETAIN PERSISTENT are treated in a particular way:
INTERNAL/EXTERNAL
The menus have the same structure.
DISPLAY: calling the DISPLAY function by pressing the MSS will
display the names of programs stored in the memory:
Only three program names can be displayed. If there are more
programs in the memory, they can be displayed by turning the
MSS. If there is a period character next to the first program name,
this indicates that an executable version of the program is in the
working memory. You can reach the menu above by pressing the
MSS if the cursor is flashing next to a program name. You must
then press the MSS once more.
ACTIVATE: If there are several programs on the hard disk of the
PLC or on the CompactFlash card, you can use this command to
activate a bootable program. A program that is already activated
will be deactivated. A program that is currently being processed
will continue to run.
Every time the XC600 is switched on and the LOAD or REBOOT
menu items are called, the PLC generates an executable program
from the activated program and stores it in the working memory.
This will overwrite any executable program that is present.
The program in the working memory can then be started.
ACTIVATE, COPY and DELETE: After calling these functions, you
will see the program name of the executable program with a
period character in front of it.
X Turning the MSS further will display all programs stored in the
memory in turn.
X Select a program by pressing the MSS.
X Turn the MSS so that the menu item ENTER appears instead of
menu item BACK.
X Press the MSS.
The function will be executed and you will reach the menu above.
COPY: The COPY command is used to copy the program between
the individual types of memoryCopy:
Hard disk <-> CompactFlash card.
DELETE: After calling EXTERNAL/INTERNAL, the DELETE function
displays the first bootable program located on the hard disk
(internal) or on the CompactFlash card (external). If the memory
contains severalprograms, they are displayed in turn by turning the
MSS. They can be deleted in turn. After the program name
appears, press the MSS and turn it until ENTER is shown. Then
press the MSS once more. The delete operation is then executed
and the next higher menu is displayed.
LOAD
After the LOAD menu is called, the PLC will create an executable
program from the activated program which it will store in the
working memory.
This will overwrite any executable program that is present. The
program in the working memory can then be started.
Declared
variables
RESET
WARM COLD HARD
RETAIN Initialised
PERSISTENT Initialised ––
RETAIN
PERSISTENT
–– Initialised
PROGRAM:
RESET
INTERNAL
EXTERNAL
LOAD
BACK
RESET:
WARM
COLD
HARD
BACK
PROG-INTERN:
DISPLAY
ACTIVATE
COPY
DELETE
BACK
PROGNAM1
PROGNAM2
PROGNAM3
BACK
h
An activated program is always warm started on startup.