Hardware and Engineering
12/01 AWB2700-1428GB
16
XC-SYS1 operator module
The operator module always forms the final component of several
stacked modules, and provides access to the controller.
Task
The operating mode selector switch (OMS) is used to select oper-
ating states MRES, STOP, RUN or RUN-P. The current PLC status is
indicated by the three LEDs. Parameters such as time and pass-
word, the current PLC states are shown on the display. You can
use the menu selection switch (MSS) to enter passwords and
modify specific states. Entry is menu-guided.
Setup
Operating mode selector switch (OMS)
The operating mode selector switch sets thestatus that the PLC
assumes after the power supply is switched on. If you wish to
change the switch position with the power supply switched on, the
PLC will switch to the new status.
You can select one of the four settings. After the power supply
voltage is switched on, the PLC executes the following function:
Figure 28: Setup of the operator module
a LED STOP
b LED RUN
c SF LED
d Display
e Operating mode selector switch (OMS)
f Menu switch
g Battery
h Eject button for CompactFlash card
i CompactFlash card
a
bc
d
e
f
h
g
i
STOP RUN
RUN
RUN-P
STOP
MRES
SF
Position Function
RUN The user program is processed. A debugging or status
change initiated from the PC is not possible.
RUN-P The user program is processed. All access functions are
available via the programming device.
STOP The user program is not processed. A program can be
loaded, started or stopped.
MRES The simple variables and POU variables and those
assigned with RETAIN will be initialised.