Hardware and Engineering
12/01 AWB2700-1428GB
14
X Assign the memory range beginning with start address CE000
to the first module (CANopen or PROFIBUS-DP) to be
configured.
The input/output devices assigned to this module are connected to
the module bus system via address CE000.
X Assign the range starting with address CC000 to the second
module and D4000 to the third.
Bus terminating resistors
Bus terminating resistors must be provided at both ends of the
cable.
XC-NET-CAN CANopen module
General
The module provides the ISO 11898 interface between the CPU
module and the CANopen bus.
Task of the module
The module provides the master function for CANopen bus. It
organises and operates the data exchange between the user
program and the connected slaves. Up to 126 nodes can be
connected to a line.
The CANopen modules can be fitted between the power supply
module and the CPU module. Up to three modules (PROFIBUS-DP
or CANopen) can be fitted.
Engineering
CANopen interface
The module can be connected to the CANopen bus via the isolated
ISO 11898 interface.
Pin assignment
Connector assignment in accordance with the CiA DS 102
(CAN Physical Layer for Industrial Applications) standard.
Power supply
The power supply module provides the 5 V supply to the modules
via the PC/104 bus.
Set the system power supply so that the connected remote stations
on the CANopen line are switched on simultaneously or before the
controller. This prevents any errors occurring during the starting of
the CANopen line.
Start/Stop behaviour
Setting the OMS to the STOP position will cause all the outputs of
the remote devices to be set to 0.
An interruption on the line will cause all inputs of the disconnected
devices (receive data) to be interpreted by the PLC as 0 signals and
the outputs set by the PLC in the output module to be reset.
Devices that are still connected with the PLC will continue to be
interrogated.
Configuring the module address
Up to three XC-NET-DP-M (PROFIBUS-DP) or XC-NET-CAN
(CANopen) modules can be used in any combination. Reserve a
memory range for each module in the CPU by defining a module
address for each one:
X Set the address for each module using the jumpers in the
jumper field from range 13 to 17 (a following figures).
Figure 20: Example configuration with three modules and the
assigned addresses
h
When using the ZB4-209-DS2 PROFIBUS plug, the bus
terminating resistor can be enabled or disabled via the
slide switch on the plug.
Figure 21: CANopen interface
Figure 22: Pin assignment of the CANopen interface
SUB-D plug
connector
Signal Meaning
2 CAN_L CAN_L bus cable
3 CAN_GND CAN reference potential
7 CAN_H CAN_H bus cable
34125
8967