12/01 AWB2700-1428GB
XC-ADP/XC-ADP-XION base
modules
11
These functions were implemented by adapting the UPS device
supplied by Konzept to the power supply modules of the XC600.
When using a different UPS device, the wiring must be adapted
accordingly.
XC-ADP/XC-ADP-XION base modules
General
A base module and a power supply module form one unit. The
following table shows the combination possibilities of both
modules. The modules only differ in their capability for expansion
with XI/ON modules.
A base module provides the platform for the other function
modules that are fitted on. The complete unit is then fitted on the
mounting rail.
Task of the XC-ADP-XION module
The module controls the XI/ON data bus and provides the power
supply (5 V) to the XI/ON modules. The base module has a sepa-
rate connection for the 24 V DC field power supply of the XI/ON
modules. It also has a C connection to which the potential for the
C rails of the XI/ON modules can be connected.
How to expand the controller with XI/ON modules is described in
the XI/ON manuals, Hardware and Engineering, e.g.
AWB2700-1394.
Task of the XC-ADP module
This is used as a platform for other modules.
Engineering the XC-ADP-XION base module
Power supply for the XI/ON modules
The 24 V DC power supply required for the load supply of the XI/
ON modules is connected to the base module (a also Power
supply module). The maximum current consumption is 10 A.
Connections
The C1 connection is routed to the XI/ON modules. It is used for
providing an additional common potential, e.g. PE.
XI/ON modules that have a C in their designation, e.g. S4T S-B-C-
S, require the provision of a common C rail.
Figure 10: Delayed switching of the power supply
a UPS device
Base module Power supply module Expansion
XC-ADP XC-POW50-UPS XI/ON
XC-ADP-XION XC-POW50-XION-UPS
L1
N
PE
L1
N
PE
K1T
K1T
a
XC600
Figure 11: Connections between the XC-ADP-XION base module
and the XI/ON modules
a 5 V DC from the power supply module
b Data from the supply module
c Field supply 24 V DC
d C rail connection
Figure 12: 24 V DC and C1 connections of the XC-ADP-XION
a 24 V DC connection
b C rail connection
c Plug-in terminals, connection cross-sections:
flexible with ferrule 0.5 mm
2
to 2.5 mm
2
solid 0.5 mm
2
to 2.5 mm
2
Warning!
The maximum load on the C rail and C1 connection is
24 V!
XI/ON modulesXC-ADP-XION
ab
cd
Field
Supply
24V 0V
11
C
1