12/01 AWB2700-1428GB
XC-NET-CAN CANopen module
15
Assign the input/output address range (%IB/%QB) to the module
in the PLC configuration in XSoft:
The modules are integrated in turn into the PLC configuration:
Assign the memory range beginning with start address CE000 to
the first module (CANopen or PROFIBUS-DP) to be configured. The
input/output devices assigned to this module are connected to the
module bus system via address CE000. Assign the range starting
with address CC000 to the second module and D4000 to the third.
Bus terminating resistors
120 O bus terminating resistors must be provided at the ends of
the networks. Standard plugs are available that allow the bus
terminal resistor to be enabled or disabled via a slide switch on the
plug, e.g. the SUBCON-PLUS-CAN plug from Phoenix Contact,
Order No. 2744694
Only use CANopen-approved cable with the following features:
Ripple resistance 108 to 132 O
Capacitance < 50 pf/m
1. r CE000*
Figure 23: Address setting of module 1
* Factory setting
2. r CC000
Figure 24: Address setting of module 2
3. r D4000
Figure 25: Address setting of module 3
111
171615
14
13
00
011
171615
14
13
00
010
171615
14
13
10
Figure 26: Example configuration with three modules and the
assigned addresses
Figure 27: CANopen cable
Baud rate
[kbits/s]
F Length
[m]
Cable cross-section
[mm
2
]
Loop
resistance
20 1000 0.75 to 0.80 16 O/km
125 500 0.50 to 0.60 40 O/km
250 250 0.50 to 0.60 40 O/km
500 100 0.34 to 0.60 60 O/km
1000 40 0.25 to 0.34 70 O/km
CAN_H
CAN_GND
CAN_L
CAN_H
CAN_GND
CAN_L
120 O
120 O