Menu Overview of the Oper-
ator Module
12/01 AWB2700-1428GB
42
Basic menu
After the power supply is switched on or after a reboot, the display
shows messages relating to the startup operation. After a startup
the basic menu may show the following messages:
The first line shows the time as well as diagnostics diagnostics
(!), whether password protection is active (+) and the status of the
PLC (P = RUN-P).
The second line shows the current status of the PLC.
The third line shows the name of the executable program. If there
is no executable program in the PLC, the message PROG: ??? is
displayed.
If the cursor is positioned next to MAIN MENU, you can turn the
menu selector switch to PASSWORD (if one has been selected) or
DISPLAY and select the item by pressing the switch.
The MAIN MENU can be reached by positioning the cursor on this
menu item and pressing the MSS.
Use menu item BACK to return to the basic menu.
DISPLAY menu
a also: Display a text from the user program.
The first three lines (3 x 12 characters) of the DISPLAY menu are
reserved for displaying information from the user program.
The function must be permanently selected to execute this feature.
To do this turn the MSS in the basic menu to menu item DISPLAY.
Press the MSS and the display will be cleared when the PLC is in
Stop status and will show the text when the PLC is in Run.
Use BACK to return to the basic menu.
MAIN MENU
MAIN MENU: DIAGNOSTICS
Calling this menu will display the following menu items:
EVENT
An event that has occurred is indicated in the basic menu by an
exclamation mark on the display. The messages are shown with
the time and date, e.g.:
The most recent message is always displayed. Previous messages
can be displayed by turning the MSS.
ERROR
Same operation as in the section EVENT.
An error that has occurred is indicated by the SF LED (central
error).
CLEAR
All the event and error messages are deleted.
Time, diagnostics
PLC status
Program name
MAIN MENU
+ = Locked with a password
P = PLC status RUN-P
(!) An exclamation mark indicates the presence of an unacknow-
ledged event message. The type of event is shown in the diag-
nostics menu under menu item EVENT, together with the time
and date the error occurred. The exclamation mark will be
cleared as soon as the EVENT menu is called.
This message and any other messages present can be cleared
via menu item DELETE.
(+) A + character is displayed if access is password protected.
In this case, the main menu cannot be called until you have
entered the password. After the correct entry has been made,
the main menu will open.
Entering an incorrect password will return you to the
PASSWORD menu.
(X) The displayed letters S = STOP, P = RUN-P, R = RUN correspond
to the position of the operating mode selector switch.
This status information can be different to the information in
the second line. A closed or open rectangle indicates that the
OMS is set to MRES.
15:21:10 !+P
RUN-P
SAWING.PRO
>MAIN MENU
MAIN MENU:
DIAGNOSTICS
PROGRAM
RECIPE
DEVICE
SYSTEM
BACK
DIAGNOSTICS:
EVENT
ERROR
CLEAR
BACK
27.07_18:35