12/01 AWB2700-1428GB
5
1 Hardware and Engineering
Setup
The XC600 PLC has a modular design. The basic unit consisting of
the base, power supply, CPU and operator modules can be
expanded with function modules for communication. Modules for
the standard PROFIBUS-DP and CANopen networks are therefore
provided for this purpose. They provide the controller with access
to the I/O devices that log process data signals and control
actuators.
The process signals can also be connected locally with XI/ON input
and output modules. This requires the use of the power supply
module with the integrated XI/ON interface and the base module
with the XI/ON adapter.
A module consists of a circuit board that is embedded in a frame.
The special frame design makes it possible to stack the modules
together, thus allowing compact functional units to be combined
to suit the requirements of the task at hand.
The circuit boards of the individual function modules meet the
requirements of the PC/104+ specification. In addition to dimen-
sions, the specifications also stipulate the requirements of the
PC/104+ bus that connects the modules. This bus also carries the
power supplies from the power supply module to the individual
function modules.
A configuration containing XI/ON input/output modules must
always include theXC-ADP-XION base module with the
XC-POW50-XION-UPS power supply module. The power supply
module adapts the PC/104+ bus to the XI/ON module bus using
the XI/ON interface. This bus is connected out from the base
module. The adapter on the base module provides the interface to
the XI/ON modules. The 24 V DC field power supply of the XI/ON
modules is also connected to the base module.
XC600 Base module Power supply
module
Without XI/ON
connection
XC-ADP XC-POW50-UPS
With XI/ON connection XC-ADP-XION XC-POW50-XION-UPS
Figure 1: Order of modules
a XC-ADP/XC-ADP-XION base module
b XC-POW50-UPS/XC-POW50-XION-UPS power supply module
c, d, e XC-NET-DP-M PROFIBUS-DP module*
or XC-NET-CAN CANopen module *
f XC-CPU601-ExM CPU module*
g XC-SYS1 operator module*
* Function modules
c d e f g b a